Fire extinguishers are among the most visible pieces of safety equipment in any workplace. They sit on brackets along corridors, near fire doors and at exit points, walked past by staff every day and thought about only when something looks off. The servicing schedule attached to each one is often the least understood part, so a clear picture of what a service covers, how often it is needed, and what you can check yourself is worth having.
How Often Do Fire Extinguishers Need to Be Serviced?
Fire extinguisher servicing follows a three-tier schedule set out in BS 5306-3:
- A monthly visual inspection, carried out on site by the responsible person or a nominated colleague
- An annual basic service by a competent person
- An extended service or overhaul at longer intervals, depending on the extinguisher type
The extended service is typically five-yearly for water, foam and powder extinguishers, and ten-yearly for CO2 and primary-sealed powder units. The underlying duty to keep fire-fighting equipment maintained sits with the responsible person under Article 17 of the Regulatory Reform (Fire Safety) Order 2005.
What Should Be Included in a Monthly Fire Extinguisher Check?
The monthly check is a visual inspection you can carry out in-house, with no specialist tools needed. Drawing on BS 5306-3, work through each extinguisher and confirm:
- It is in its designated location, visible and unobstructed
- The operating instructions are clean, legible and facing outwards
- There are no obvious signs of damage or missing parts
- The pressure gauge or indicator reads within the operational range
- The safety pin, tamper seal and any tamper indicators are intact
Record the check in your fire logbook and flag anything that needs a competent engineer’s attention before the next annual service. Catching a dropped pressure gauge or a blocked extinguisher early is exactly what these checks are for. Logging them is part of how businesses stay compliant and minimise fire risks, and many teams fold the walk-round into the same visit as their emergency lighting checks. In higher-risk premises such as commercial kitchens, booking regular fire extinguisher servicing for restaurants keeps cover in step with how hard the equipment is worked.
What Does a Basic Annual Fire Extinguisher Service Involve?
The annual basic service is carried out on site by a competent, enhanced DBS-checked engineer, and goes further than the monthly check. On arrival, the engineer signs in, reviews your site’s fire procedures and confirms the scope of work, then locates every extinguisher against your fire logbook. Each unit is checked against its type and rating, with accessibility and signage reviewed.
From there, the engineer inspects the pressure gauge, the weight of CO2 units, the hose, horn and seals, and the tamper seal and pin, and checks for corrosion or damage along with installation height and bracket security. Components are replaced where required. The unit is not discharged during a basic service. Each visit is recorded in detail as a full fire extinguisher inspection, so you have a clear picture of the condition of every unit.
Once the work is done, extinguishers are refitted to their brackets; service labels are updated, and your fire logbook is brought up to date. Any damaged, discharged, out-of-date or unsuitable equipment is clearly recorded, and your responsible person is informed of any defects or replacement needs. Our engineers carry out this work at sites across the country, including fire extinguisher servicing in London and other major cities.
When Is an Extended Service or Overhaul Required?
The extended service goes further again. The extinguisher is discharged under controlled conditions, internally inspected, its media replaced and then re-pressurised, all in line with the manufacturer’s specification. When it falls due depends on the type of extinguisher:
- Water, foam and powder extinguishers: an extended service every five years
- CO2 and primary-sealed powder units: every ten years
CO2 cylinders sit on the longer cycle because the ten-year service involves a pressure test of the cylinder itself, and primary-sealed powder units are factory-sealed to limit internal contamination, so they do not need opening as often. No extinguisher lasts forever either. Most units have a working life of around five to ten years, after which replacement is more sensible than further servicing.
Book Your Fire Extinguisher Service with Hawkesworth
Once the schedule is set, keeping fire extinguishers serviced is straightforward. Our servicing is carried out by competent, enhanced DBS-checked engineers, and you receive electronic service documentation and certification after every visit, clear quotations for any replacements, and reminders ahead of your next service date. Tell us about your sites and equipment and we will build a fire extinguisher servicing programme that fits your operation. Request a quote and we will handle the scheduling.